updates to pumping station control method
This commit is contained in:
@@ -418,19 +418,36 @@
|
||||
}
|
||||
},
|
||||
"levelbased": {
|
||||
"thresholds": {
|
||||
"default": [30,40,50,60,70,80,90],
|
||||
"rules": {
|
||||
"type": "array",
|
||||
"description": "Each time a threshold is overwritten a new pump can start or kick into higher gear. Volume thresholds (%) in ascending order used for level-based control."
|
||||
}
|
||||
},
|
||||
"timeThresholdSeconds": {
|
||||
"default": 5,
|
||||
"startLevel": {
|
||||
"default": 1,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "Duration the volume condition must persist before triggering pump actions (seconds)."
|
||||
"description": "start of pump / group when level reaches this in meters starting from bottom."
|
||||
}
|
||||
},
|
||||
"stopLevel": {
|
||||
"default": 1,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "stop of pump / group when level reaches this in meters starting from bottom"
|
||||
}
|
||||
},
|
||||
"minFlowLevel": {
|
||||
"default": 1,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "min level to scale the flow lineair"
|
||||
}
|
||||
},
|
||||
"maxFlowLevel": {
|
||||
"default": 4,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "max level to scale the flow lineair"
|
||||
}
|
||||
}
|
||||
},
|
||||
|
||||
Reference in New Issue