forked from RnD/pumpingStation
updates to safety features
This commit is contained in:
@@ -65,6 +65,13 @@ class nodeClass {
|
||||
refHeight: uiConfig.refHeight,
|
||||
minHeightBasedOn: uiConfig.minHeightBasedOn,
|
||||
basinBottomRef: uiConfig.basinBottomRef,
|
||||
},
|
||||
safety:{
|
||||
enableDryRunProtection: uiConfig.enableDryRunProtection,
|
||||
dryRunThresholdPercent: uiConfig.dryRunThresholdPercent,
|
||||
enableOverfillProtection: uiConfig.enableOverfillProtection,
|
||||
overfillThresholdPercent: uiConfig.overfillThresholdPercent,
|
||||
timeleftToFullOrEmptyThresholdSeconds: uiConfig.timeleftToFullOrEmptyThresholdSeconds
|
||||
}
|
||||
};
|
||||
|
||||
|
||||
@@ -103,10 +103,19 @@ class PumpingStation {
|
||||
return;
|
||||
}
|
||||
|
||||
//get threshholds from config
|
||||
const timeThreshhold = this.config.safety.timeleftToFullOrEmptyThresholdSeconds; //seconds
|
||||
const triggerHighVol = this.basin.maxVolOverflow * ( this.config.safety.overfillThresholdPercent/100 );
|
||||
const triggerLowVol = this.basin.minVol * ( this.config.safety.dryRunThresholdPercent/100 );
|
||||
const {
|
||||
enableDryRunProtection,
|
||||
dryRunThresholdPercent,
|
||||
enableOverfillProtection,
|
||||
overfillThresholdPercent,
|
||||
timeleftToFullOrEmptyThresholdSeconds
|
||||
} = this.config.safety || {};
|
||||
|
||||
const dryRunEnabled = Boolean(enableDryRunProtection);
|
||||
const overfillEnabled = Boolean(enableOverfillProtection);
|
||||
const timeProtectionEnabled = timeleftToFullOrEmptyThresholdSeconds > 0;
|
||||
const triggerHighVol = this.basin.maxVolOverflow * ((Number(overfillThresholdPercent) || 0) / 100);
|
||||
const triggerLowVol = this.basin.minVol * (1 + ((Number(dryRunThresholdPercent) || 0) / 100));
|
||||
|
||||
// trigger conditions for draining
|
||||
if(direction == "draining"){
|
||||
@@ -116,7 +125,10 @@ class PumpingStation {
|
||||
`direction=${String(direction)}; triggerLowVol=${Number.isFinite(triggerLowVol) ? triggerLowVol.toFixed(2) + ' m3' : 'N/A'}`
|
||||
);
|
||||
|
||||
if( (remainingTime < timeThreshhold && remainingTime !== null) || vol < triggerLowVol || vol == null){
|
||||
const timeTriggered = timeProtectionEnabled && remainingTime != null && remainingTime < timeleftToFullOrEmptyThresholdSeconds;
|
||||
const dryRunTriggered = dryRunEnabled && vol < triggerLowVol;
|
||||
|
||||
if (timeTriggered || dryRunTriggered) {
|
||||
//shut down all downstream or atequipment machines,pumping stations and machine groups
|
||||
Object.entries(this.machines).forEach(([machineId, machine]) => {
|
||||
const position = machine?.config?.functionality?.positionVsParent;
|
||||
@@ -142,7 +154,11 @@ class PumpingStation {
|
||||
`remainingTime=${Number.isFinite(remainingTime) ? remainingTime.toFixed(1) + ' s' : 'N/A'}; ` +
|
||||
`direction=${String(direction)}; triggerHighVol=${Number.isFinite(triggerHighVol) ? triggerHighVol.toFixed(2) + ' m3' : 'N/A'}`
|
||||
);
|
||||
if( (remainingTime < timeThreshhold && remainingTime !== null) || vol > triggerHighVol || vol == null){
|
||||
|
||||
const timeTriggered =timeProtectionEnabled &&remainingTime != null && remainingTime < timeleftToFullOrEmptyThresholdSeconds;
|
||||
const overfillTriggered = overfillEnabled && vol > triggerHighVol;
|
||||
|
||||
if (timeTriggered || overfillTriggered) {
|
||||
//shut down all upstream machines,pumping stations and machine groups
|
||||
Object.entries(this.machines).forEach(([machineId, machine]) => {
|
||||
const position = machine?.config?.functionality?.positionVsParent;
|
||||
@@ -476,6 +492,7 @@ class PumpingStation {
|
||||
|
||||
|
||||
_onLevelMeasurement(position, value, context = {}) {
|
||||
this.measurements.type('level').variant('measured').position(position).value(value).unit(context.unit);
|
||||
const levelSeries = this.measurements.type('level').variant('measured').position(position);
|
||||
const levelMeters = levelSeries.getCurrentValue('m');
|
||||
|
||||
@@ -1014,7 +1031,7 @@ if (require.main === module) {
|
||||
const inflowSensor = new Measurement(createFlowMeasurementConfig('InfluentFlow', 'in'));
|
||||
const outflowSensor = new Measurement(createFlowMeasurementConfig('PumpDischargeFlow', 'out'));
|
||||
|
||||
//station.childRegistrationUtils.registerChild(levelSensor, levelSensor.config.functionality.softwareType);
|
||||
station.childRegistrationUtils.registerChild(levelSensor, levelSensor.config.functionality.softwareType);
|
||||
//station.childRegistrationUtils.registerChild(inflowSensor, inflowSensor.config.functionality.softwareType);
|
||||
//station.childRegistrationUtils.registerChild(outflowSensor, outflowSensor.config.functionality.softwareType);
|
||||
|
||||
@@ -1023,7 +1040,7 @@ if (require.main === module) {
|
||||
|
||||
// Seed initial measurements
|
||||
|
||||
//seedSample(levelSensor, 'level', 1.8, 'm');
|
||||
seedSample(levelSensor, 'level', 1.8, 'm');
|
||||
//seedSample(inflowSensor, 'flow', 0.35, 'm3/s');
|
||||
//seedSample(outflowSensor, 'flow', 0.20, 'm3/s');
|
||||
|
||||
|
||||
Reference in New Issue